Browse Categories

ALTRONIX CORPORATION NAC 12/24VDC@8A 10OUT W/RED ENCL

Item #: AL-AL842ULADA

Product Info

ALAL842ULADA
ALTRONIX CORPORATION
AL842ULADA

NAC POWER EXTENDER 24/12VDC@8 AMP. (4)CLASS A OR (4)CLASS B NAC CIRCUITS. GENERATES SYSTEM SENSOR GENTEX FARADAY AND AMSECO SYNC PROTOCOLS. (2) 1 AMP AUX. OUTPUT. UL LISTED FIRE (UL864 UL1481) MEA/CSFM/FM APPROVED. RED ENCLOSURE 18“H X 14.5?W X 4.625?D

Altronix AL842ULADA is an extremely cost effective voltage regulated remote NAC Power Extender. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC) expansion (supports ADA requirements) and providing auxiliary power to support system accessories.

Features
2-wire horn/strobe Sync mode allows audible notification appliances (horns) and visual notification appliances (strobes) to be silenced/deactivated at the same time.
Sync protocols include Potter/Amseco, Gentex®, System Sensor®, and CooperWheelock®.
Temporal Code 3, Steady Mode, Input to Output Follower Mode (maintains synchronization of notification appliances circuit).
Compatible with 24VDC fire panels.
Output loop supervision steered to Input 1 or Input 2.
Signal circuit trouble memory (helps identify intermittent loop problems).
Common trouble input and output for external trouble signals tie-in.
Ground fault detection.
Input
Voltage:
120VAC, 60Hz, 5A.
Two (2) Class A or two (2) Class B inputs.
Two (2) NC dry contact trigger inputs.
Input Ratings (INP1 and INP2):
8-30VDC 6.5mA max from FACP.
12V 6.5mA, 24V 6.5mA from FACP.
Output
Voltage:
24VDC power-limited outputs.
Current:
8A max. total alarm current.
2.5A max. current per output.
Auxiliary:
Two auxiliary outputs rated at 1A each (1A continuous, 1A AC disconnect).
Other:
Thermal and short circuit protection with auto reset.
Filtered and regulated outputs.
Programmable Supervised Indicating Circuit Outputs:
Four (4) Class B, or Four (4) Class A, or
Two (2) and Two (2) Class B.
Battery Charging
Built-in charger for sealed lead acid or gel type batteries.
Automatic switchover to stand-by battery when AC fails.
Zero voltage drop when switching over to battery backup.
(Batteries are sold separately).
Supervision
AC Failure: Form “C” contacts.
Battery: Form “C” contacts.
Indicators (LED)
AC Power (Green): Input voltage is present.
DC Output (Red): Powered.
Logic Board (Red and Green): Output status.
Temperature
Operating: 0° C to 49° C (32° F to 120° F).
Storage: – 20° C to 70°C ( – 4° F to 158° F).
Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.): 31 BTU/Hr.
Enclosure:
Wall mount enclosure for indoor use.
Dimensions 14.5“W x 18“H x 4.62“D (368 mm W x 457 mm H x 118 mm D).
1/2” and 3/4” combination knocko

NOT IN STOCK
QTY:

Have Questions?

Ask our experts: