ALTRONIX CORPORATION TROVE2PX2/8DR/ULX/10A/FUSE
Product Info
TROVE2PX2/8DR/ULX/10A/FUSE
Altronix T2PXK78 kit consists of Trove2 enclosure, TPX2 Paxton/Altronix backplane with one (1) 24VDC @ 10A power supply/charger, one (1) fuse protected eight (8) output access power controller and one (1) fuse protected eight (8) dual output power distribution module and one (1) voltage regulator. This kit also accommodates Paxton Net2 Plus boards for up to eight (8) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.
AL1024ULXB2 Power Supply/Charger
Input
Voltage: 115VAC 60Hz, 4.2A max.
Main Fuse: 5A / 250V.
Outputs
Voltage: 24VDC.
Current: 10A @ 24VDC continuous max.
Other: Overvoltage protection. Filtered and regulated.
Battery Charging
Capacity: 12VDC/12AH (2 within enclosure); 40 AH / 65 AH (requires separate enclosure)
Type: Sealed lead acid or gel type
Failover: Upon AC loss, instantaneous
(Batteries are sold separately).
Supervision
AC Failure: Form “C” contacts.
Battery: Form “C” contacts.
Indicators LED
Input: 115VAC is present.
DC Output: Powered.
Battery: Discharged or not connected.
ACM8 Access Power Controller
Input
Voltage: 24VDC from AL1024ULXB2.
Main Fuse: 10A / 32V.
Outputs
Voltage: 12VDC.
Eight (8) 24VDC independently controlled fused outputs:
a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above.
Output Fuses: 3.5A / 32VDC.
Indicators (LED)
Red LEDs: Outputs are triggered (relays energized).
Green LED: FACP disconnect is triggered.
VR6 Voltage Regulator
Input/Output
Voltage Range: 24VDC 10A = Output: 12VDC
6A.
Output
12VDC regulated output.
Output rating 6A max.
Surge suppression.
Indicators LED
Input: Indicates input voltage is present.
Output: Indicates normal operating condition.
PDS8 Dual Input Power Distribution Module
Input
Voltage Range: 5VDC to 24VDC, up to 10A each, 20A total input.
Main Fuse: 10A.
Outputs
Fuse protected outputs rated @ 3A per output, non power-limited. Total output 20A max.
Do not exceed the individual power supply ratings.
Any of the eight (8) fuse protected power outputs are selectable to follow power Input 1 or Input 2.
Individual outputs may be set to OFF position for servicing.
Outputs Ratings
4.8VDC – 24VDC.
Indicators (LED)
DC Output: Individual voltage LEDs indicate.
12VDC (Green) or 24VDC (Red/Green)
Features
Multiple units may be daisy-chained to accommodate larger systems.
Environmental
Temperature
Operating: 0°