MACURCO INC. CARBON MONOXIDE CO (LOW VOLTAGE) FIXED G
Product Info
CARBON MONOXIDE CO (LOW VOLTAGE) FIXED GAS DETECTOR CONTROLLER TRANSDUCER
The Macurco 6 Series fixed gas detectors provide life-saving solutions to protect people and property. These fixed gas detectors are designed for low-level detection, mitigation, and notification. Let these detectors do the work for you by shutting off valves, turning on fans, engaging horns and strobes, and providing notification to fire panels and building automation systems when gases reach vital limits.
Features:
Easy installation to 4×4 electrical boxes via mud plate
User selectable settings (Default to industry standards) via two-button interface
5 A SPDT fan relay, 0.5A alarm relay to control fans, valves, louvers, horn and strobes
4-20mA output to control VFDs and send to BMS
LED display to show gas concentrations easily
End of life notification
Field calibration kits available
Applications:
Parking garages
Mechanical rooms
Restaurants
Battery charging stations
Breweries
Storage facilities
Loading docks
Warehouses
Firehouses & ambulance bays
Refrigeration facilities
Vehicle repair facilities
Bus depots
Specifications:
Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
Current @ 24 VDC: 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA stand by
Shipping Weight: 1 pound (0.45 kg)
Size: 4 1/2 × 4 × 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
Color: Dark gray
Connections: plugs/terminals
Mounting box: (not included) 4×4 electric
Fan relay: 5 A, 240 VAC, pilot duty, SPDT
Fan relay actuation: selectable at 25 ppm, 35 ppm (default), 50 ppm or 100 ppm CO
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
Fan Minimum Runtime settings are OFF (default), 3, 5, 10 or 15 minutes
Alarm relay: 0.5A 120 V, 60 VA
Alarm relay actuation: selectable N.O. default or N.C.
Alarm relay settings: OFF, 50 ppm, 100 ppm, 150 ppm and 200 ppm (default)
Current Loop, 4-20 mA for 0-200 ppm CO
Operating Environ: 0F to 125 F (-18C or above 52C) 10 to 90% RH