POTTER HEAT DETECTOR,135DEG.,ROR,N.C.
Product Info
The CR Series detectors are combination Rate-of-Rise and Fixed Temperature. The Rate-of-Rise function allows the detector to operate when the temperature at the detector increases at a rate of 15°F per minute. The Fixed Temperature portion will cause the detector to operate when it reaches the applicable temperature. The Rate-of-Rise portion of the detector is restorable; however the Fixed Temperature portion is non-restorable.
Features
Low profile design
Dual action (rate of rise/fixed temperature) or fixed temperature only
White plastic housing
Up to 70’ inter detector spacing
Open or closed contact versions available
Available in single or multiple circuit versions
Product includes a 5 year warranty
Specifications:
Dimensions: 5.25 × 2
Device Weight: 0.41 lbs (0.19 kg)
Shipping Weight: 0.6 lbs (0.3 kg)
Materials: Plastic
Contact Ratings: 3 Amps at 125VAC, 1 Amp at 28VDC, 0.3 Amps at 125VDC
Environmental Limitations: -20F (-30C) – 250F (120C), Exclusive of Operating Temperature
Mounting: 4 Octagon Backbox