PAD 100 SINGLE INPUT MODULE
Product Info
The PAD100-SIM uses one (1) SLC loop addresses when monitoring one (1) Class B circuit. The module mounts on either a 4” square or double gang box. The module is capable of monitoring one (1) Class B circuit. The PAD100-SIM includes one red LED to indicate the module’s status. In normal condition, the LED flashes when the device is being polled by the control panel. When the input is activated, the LED will flash at a fast rate.
Features:
One (1) Class B monitoring input
SLC Class a, Class X & Class B
Mounts in a standard 4” or double gang box
Wiring terminals accessible when mounted in box
All wiring terminals accept 22 to 12 aWg
Product includes a 5 year warranty
UUKL Listed for Smoke Control
NOTE: This addressable module does not support 2-wire smoke detectors.
Specifications:
Operating Voltage – 24.0V
Max SLC Standby Current – 240?A
Max SLC Alarm Current – 240?A
Max Wiring Resistance of IDC – 100 ?
Max Wiring Capacitance of IDC – 1?F
EOL Resistor – 5.1K ?
Operating Temperature Range – 32 to 120°F (0 to 49°C)
Operating Humidity Range – 0 to 93% (non-condensing)
Max no. of Module Per Loop – 127 units
Dimensions – 4.17” (106mm)L x 4.17” (106mm)W x 1.14” (29mm)D
Mounting Options – Standard 4” Square or Double Gang Box
Shipping Weight – 0.6 lbs