SIGNALINK BRIDGE WIRELESS SYST
Product Info
The SignaLink Bridge Wireless Supervisory System can monitor any dry-contact switch such as tamper or flow switches and transmit their status wirelessly to any fire alarm panel. SignaLink Bridge uses a wireless transmitter, installed with the switch being monitored, and a wireless receiver, installed with the fire alarm panel, to fully monitor the switch’s state.
Features:
UL 864 10th edition and ULC S527 Listed
Fully supervised wireless communication bridge between all dry contact devices
2.4 GHz communication format
Transmitter works on any dry contact product not listed as explosion proof
Receiver provides dry contact output, compatible with any fire panel/ fire alarm system
Eliminates the need for extensive wiring/conduits
Specifications:
WTX-M Transmitter
Conduit Connection – ½” NPT male
Enclosure – UV and Impact resistant Polycarbonate
Environmental Limitations – Indoor/Outdoor NEMA 4 / IP66 -40°F to 150°F (-40°C to 66°C)
Max Circuit Current – 28uA
Max Circuit Voltage – 3 VDC
Power Requirement – Two AA size Energizer 1.5 volt Lithium Iron/Disulfide battery model L91, 3000 mAh
Reference Level – Maximum Ambient noise level allowed: -37 dBm
Service Use – NFPA 13, 13D, 13R and 72
Weight – 0.5 lbs (0.23 KG)
WRX-R Receiver
Conduit Connection – Opening for 1/2” conduit, terminals for 12-22 AWG wires
Contact Rating – Common Alarm/Supervisory Relay: 1A at 30 VDC
Enclosure – UV and Impact resistant Polycarbonate
Environmental Limitations – Indoor/outdoor use with standard smoked cover. Indoor use only with optional clear cover. NEMA 4 (IP66) -40°F to 150°F (-40°C to 66°C)
Power Requirement – 24VDC at 55mA Normal, 75mA in Alarm
Reference Level – Maximum Ambient noise level allowed: -37dBm
Service Use – NFPA 13, 13D, 13R, 72
Weight – 0.75lbs (0.34KG)