Silent Knight 5895XL Intelligent Power Module
5895XL intelligent power modules are 6A notification power expanders that provide their own AC power connection, battery charging circuit, and backup battery for use with Silent Knight® addressable fire alarm control panels.
127 PT SLC EXPANDER FOR AFC
The Signaling Line Circuit Expander PAD100-SLCE allows up to thirty one additional loops. Each loop adds 127 addressable sensors or modules in any combination. The PAD100-SLCE may be configured for Class A or Class B wiring without the need for additional modules. The PAD100-SLCE communicates with the control panel via the Potter P-Link communication bus. The loop adder is mounted in either the control panel cabinet, the intelligent power supply, AE-2, AE-8 or the AE-14 expander cabinet. Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting.
6 ZONE SPRINKER MONITORING PANEL RED
The PFC-6006 is a listed small conventional fire system ideally suited to monitor a small fire system such as a fire sprinkler system. The first input is selectable as a Class A or Class B water flow input and the other five zones are selectable from a menu of options including two-wire smoke detection. The panel has a 1.0 amp power supply that powers the panel, charges the batteries and supplies 0.5 amps to a notification appliance circuit and 0.5 amps of auxiliary power. The auxiliary power is programmable as constant or resettable.
The control panel is in a metal cabinet with a key lock and lexan window for viewing the system status. The printed circuit assembly is mounted for quick removal and installation to allow the cabinet to be installed with minimal effort. The cabinet houses up to two 12VDC, 18 AH batteries.
The display is a thirty-two (32) character LCD with system status LEDs. The system status is clearly displayed and the panel includes a history buffer for past events. T
Fire-Lite ANN-80 Remote Annunciator
ANN-80 remote annunciators are compact, backlit, 80-character LCD fire annunciators that mimic the fire alarm control panel (FACP) display.
IDC-6 EXPANDER / PFC-4064
The Initiating Device Circuit Expander (IDC-6) provides an additional 6 inputs per module. The panel supports up to thirty-one (31) IDC-6 modules. The circuits are power-limited and supervised. All inputs are suitable to monitor 2-wire smoke detectors. Smoke detectors shall be installed in compliance with NFPA 72. Inputs can also be used for automatic, manual, waterflow or supervisory service. The IDC-6 communicates via the PLink communication bus. The IDC-6 can be mounted in either the control panel cabinet, the intelligent power supply, AE-2, AE-8 or the AE-14 expander cabinet. Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting.
Fire-Lite 411 Series Fire Alarm Communicators
Fire Alarm Communicators designed for a variety of fire and non-fire applications
Fire-Lite ES-50XP Addressable Fire Alarm Control Panel with Built-in Cellular Communicator
The ES-50XP FACP comes with a built-in dual path (IP/cellular) and dual cellular (AT&T/Verizon) 5G LTE-M cellular communicator and supports up to 50 addressable devices in any combination of detectors or modules.
255PT ADDRESSABLE FIRE W CELL
FireLink FACP XL 255 with sole /dual path cell &/or IP communicator & annunciator built in. (4 on board NACs providing up to 6.5A notification power). Locking, Red Enclosure, (surface or flush mount), removable 16” x 25” door, with 14.25” x 16” base. Houses up
to 32Ah battery backup. For flush mount applications, use external antennas.
Fire-Lite ANN-RLY Relay Module
ANN-RLY relay modules provide 10 programmable Form C relays when used with compatible fire alarm control panels (FACPs).